ENPACK

Containerized Solutions

About Us

Our containerized energy storage system (ENCAP Storage) is the perfect solution for large-scale energy storage projects. The energy storage containers can be used in the integra- tion of various storage technologies and for different purposes. The energy storage system (ENCAP Storage) containers are designed for neighborhood’s, public buildings, medium to large businesses and utility scale storage systems, weak- or off-grid, e-mobility or as backup systems.

CONTAINERIZED SOLUTION USED WITH THE FOLLOWING APPLICATIONS

1. Microgrids Application

2. Grid Stablization Application

3. EV Charging Application

ENCAP CONTAINERIZED SOLUTIONS

Available 10ft, 20ft & 40ft Containers

ENCAP

Beyond Batteries

Smart Management

EFFICIENT

SAFE & RELIABLE

Technical data sheet

DC Energy 10kWh
Voltage Range 43.2Vdc to 60.8Vdc
DC Voltage (Nominal) 48Vdc
Internal Resistance < 4 mili Ohms

Technology Encapsulated Cell
Nominal Cell Voltage 6.4 ~6.6Vdc / Cell (Encapsulated) 1/2 + 0.12V Envelope

Maximum Continuous Charge Current 200A (~1C)
Charging Method CC/CP/VP

Maximum Continuous Discharge Current 300A (~1.5C)
Discharging Method CC/CP/VP

Module Monitoring
Total Voltage, Individual Cell Voltages, Current,
Temperatures, SOC and Energy Consumed

Operating TemperatureRange -30oC~ +70oC (See Fig.1:Temperature Specifications)
Operating Humidity Non-Condensing

Dimensions1 (W x H x D) mm 433 x 335 x 650
Weight (kg) 120
Module Casing Material GI Powdered
Terminal Type 300A Terminal Post

OLED Display Monitor Module
Communication WIFI / CANBUS / Bluetooth
Alarm
Buzzer alarm in the event of Over/under-Voltage, OverCurrent, Over Temperature
Dry Contacts Output Four programmable Dry Contacts
Dry Contacts Input 24Vdc three digital input with isolated ground

Short Circuit Protection Electronic Switching, Terminal Cut-off
Over/under Voltage Electronic Switching, Terminal Cut-off
Over Current Electronic Switching, Terminal Cut-off
Over Temperature Electronic Switching, Terminal Cut-off

Cells Projected Cycle Life2 500,000 cycles
Cells Projected Calendar Life3 25 years
Module Projected Shelf Life4 10 years
Warehousing Can be stored at any SOC without affecting cycle life

Precautions

Alarm

In case of alarm, immediately rectify/attend to the cause of the alarm.

Physical Damage

In case the Module is physically damaged due to any event, do not install and energize the Module under any circumstances and contact your Reseller or After Sales Support

Short Circuit

Ensure precautions to prevent short-circuit under all circumstances.

Galvanic Isolation

When connecting to external devices ensure that galvanic isolation of the external device(s) does not exceed 1000V.

Parallel Connection

All Modules must be at 100% SOC before connecting in parallel. There is no limit on the number of Modules that can be connected in parallel.

Series-Parallel Connection

Modules cannot be connected in series-parallel combination under any circumstance.

Notes

1 Product Dimensions are for reference only and may change without notice.

2 Projected Life of encapsulated cells.

3 Projected Calendar Life of encapsulated cells from the date of first operation.

4 Shelf Life is the Life of the Module (in years) from the date it is manufactured to the time it is first operated.

• Additional terms and conditions, including a limited warranty, will apply at the time of purchase.

• For critical applications, please contact your Reseller or After Sales Support.

Temperature

Specifications

Temperature Specifications of 10kWh 48V ENCAP Module

Contact Us

Contact Us

Official Distributor